8.3.5 System X Y E and O A communication
The cross-sectional area of each core of the communication wiring is not less than 0.75 mm2, and the length must not
exceed 1200 m.
The centralized controller and digital electric meter are optional accessories. Please contact the local dealer for
purchase if needed.
Connect the shielding nets at both ends of the shielded wire to the sheet metal “ ” of the electronic control box.
Applicable standards: EN 55014-1 and EN 55014-2. The communication line must be shielded wire.
Figure 3-8.9: X Y E and O A communication wiring configuration