EasyManuals Logo
Home>Midea>Air Conditioner>V8 Series

Midea V8 Series User Manual

Midea V8 Series
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
V8 Mini R410A VRF 50Hz
86
Midea V8 Mini Series Engineering Data Book
3.5 Refrigerant Piping Selection Example
The example below illustrates the piping selection procedure for a system consisting of an outdoor unit (160 model) and 6
indoor units (2.2 kW×1+2.8 kW×5), as shown in Figure 3-3.4. The system's total equivalent length of all liquid and gas pipes
is less than 90m.
Figure 3-3.4: Refrigerant piping selection example
Step 1: Select indoor auxiliary pipes a to f
The capacity of indoor units N1 to N6 are less than 6.3kW. Refer to Table 3-3.6. Indoor auxiliary pipes a to f are Φ12.7
/ Φ6.35.
Step 2: Select indoor main pipes (L2 to L5) and indoor branch joints B to E
Refer to Table 3-3.5
The indoor units (N1 and N2) downstream of indoor branch B have a total capacity of 2.8*2=5.6kW. Indoor main pipe
L2 is Φ15.9 / Φ9.52. Indoor branch joint B is FQZHN-01D.
The indoor units (N3 and N4) downstream of indoor branch D have a total capacity of 2.8*2=5.6kW.. Indoor main pipe
L4 is Φ15.9 / Φ9.52. Indoor branch joint D is FQZHN-01D.
The indoor units (N5 and N6) downstream of indoor branch E have a total capacity of 2.8+2.2=5.0kW.. Indoor main pipe
L5 is Φ15.9 / Φ9.52. Indoor branch joint E is FQZHN-01D.
The indoor units (N3 to N6) downstream of indoor branch C have a total capacity of 5.6+5.0=10.6kW. Indoor main pipe
L3 is Φ15.9 / Φ9.52.Indoor branch joint C is FQZHN-01D.
Step 3: Select main pipe (L1) and indoor branch joint A
The indoor units (N1 to N6) downstream of indoor branch joint A have a total capacity of 5.6+10.6=16.2kW. The system's
total equivalent length of all liquid and gas pipes is less than 90m. The outdoor units model is 160. Main pipe L1 is
Φ19.1/Φ9.52. First Indoor branch A is FQZHN-01D. Refer to Table 3-3.6.
Outdoor Unit
N1
(28)
N3
(28)
N5
(28)
N6
(22)
N2
(28)
N4
(28)
A
B
D
E
C
a
b
c
e
f
d
L1
L2
L5
L3
L4
Legend
L1
Main pipe
L2 to L5
Indoor main pipes
a to f
Indoor auxiliary pipes
A to E
Indoor branch joints
Figures in parentheses indicate indoor unit
capacity indexes.

Other manuals for Midea V8 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V8 Series and is the answer not in the manual?

Midea V8 Series Specifications

General IconGeneral
BrandMidea
ModelV8 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals