V8 Mini R410A VRF 50Hz
94
Midea
V8 Mini
Series Engineering Data Book
box continued from previous page
Piping orientation during brazing
Brazing should be conducted downwards or horizontally to avoid filler leakage.
Figure 3-4.6: Piping orientation during brazing
Piping overlap during brazing
Table 3-4.3 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints
on piping of different diameters. Refer also to Figure 3-4.7.
Figure 3-4.7: Piping overlap and gap for brazed joints
Legend
A
Inner diameter of larger pipe
D
Outer diameter of smaller pipe
B
Inlaid depth (overlap)
Table 3-4.3: Piping overlap and gap for brazed joints
1
D (mm)
Minimum
permissible B
(mm)
Permissible A – D
(mm)
5 < D < 8
6
0.05 - 0.21
8 < D < 12
7
12 < D < 16
8
0.05 - 0.27
16 < D < 25
10
25 < D < 35
12
0.05 - 0.35
35 < D < 45
14
Notes:
1. A, B, D refer to the dimensions shown in Figure 3-4.7.
Filler
Use a copper/phosphorus brazing alloy (BCuP) filler that does not require flux.
Do not use flux. Flux can cause corrosion of piping and can affect the performance of compressor oil.
Do not use anti-oxidants when brazing. Residue can clog piping and damage components.

Other manuals for Midea V8 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V8 Series and is the answer not in the manual?

Midea V8 Series Specifications

General IconGeneral
BrandMidea
ModelV8 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals