V8 Mini R410A VRF 50Hz
96
Midea
V8 Mini
Series Engineering Data Book
4.7 Direction of refrigerant pipe connection
Field piping can be connected in 4 directions. Before connecting, knock off the plate in the corresponding direction.
Figure 3-4.9: Direction of refrigerant pipe connection
Figure 3-4.10: The connection method of the forward outlet pipe
Figure 3-4.11: The connection method of the rightward outlet pipe.
Figure 3-4.12: The connection method of the downward outlet pipe.
Figure 3-4.13: The connection method of the backward outlet pipe.
4.8 Pipe Flushing
4.8.1 Purpose
To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the
system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 4.1.1 “Installation procedure”,
pipe flushing should be performed once the piping connections have been completed with the exception of the final
connections to the indoor units. That is, flushing should be performed once the outdoor units have been connected but
before the indoor units are connected.