R410A DC Inverter VRF V4 Plus Individual Series 50Hz MCAC-VTSM-2014-04
72 Installation
Increasing size as the following:
Φ9.5→Φ12.7 Φ12.7→Φ15.9 Φ15.9→Φ19.1 Φ19.1→Φ22.2 Φ 22.2→Φ25.4 Φ25.4→Φ28.6
Φ28.6→Φ31.8 Φ31.8→Φ38.1 Φ38.1→Φ41.3 Φ41.3→Φ44.5 Φ44.5→Φ54.0
When counting the total piping length, the actual length of above distribution pipes must be doubled. (Expect the main pipe
and the distribution pipes): Total piping length=1+(L2+L3+L4+L5+L6+L7+L8+L9)×2+a+b+c+d+e+f+g+h+i+j≤1000m
The length from the indoor unit to the nearest branch joint assembly or MS≤40m.a,b,c,d,e,f,g,h,I,j≤40m
The length difference between (the outdoor unit to the farthest indoor unit) and (the outdoor unit to the nearest indoor unit) ≤
40m. [(L1+L5+L8+L9+j)-(L1+L2+L3+a)]≤40m
7.3 Refrigerant piping selection
Pipe name
Indoor unit branch pipe assembly
Table1: Indoor unit branch pipe selection (a~i)
Capacity of indoor unit
(A×100W)
Branching pipe length≤10m
Branching pipe length≥10m
Table 2: Indoor unit main pipe selection (L1~L8)
Capacity of indoor unit
(A×100W)
Indoor unit main pipe (mm)