Page #6 background image
E
F
F
G
EN-5
EN
Wall
Outdoor
side
2-2. HOLE DRILLING
1) Determine the wall hole position.
2) Drill a dia. 75 mm hole. The outdoor side should be 5 to 7 mm lower than the
indoor side.
3) Insert wall hole sleeve
K.
Unit suspension procedures
Adjust the length of the bolt’s protrusion from the ceiling surface beforehand.
Check the pitch of the suspension bolt
E. (308 mm × 1051 mm)
1) Install special washer
and their nuts F onto the suspension bolt
E
in
advance.
* Do this in the following order (from the top): nut
F, special washer with
cushion
, special washer , nut F, nut
G
.
* Position special washer, with cushion
with the insulated surface pointing
down, as in the gure.
2) Lift the unit into place, aligned properly with suspension bolt
E. Pass the
bracket between special washer, with cushion
and special washer , which
are already in place, and secure it. Do the same in all four places.
* Make sure the suspension bolt
E extends 70 mm or more from the surface
of the ceiling. Otherwise you will not be able to install the grille (optional).
* If the points for securing the grille are not ush with the ceiling surface,
water may condense, or the panel may not open/close.
3) If the long opening in the bracket and opening in the ceiling do not align, adjust
them until they do.
4) Check that the four places for securing the grille are all level using a spirit
level.
5) Tighten all the nuts.
2-3. DRAIN PIPING
Use drain pipe B for drain piping. Be sure to connect the piping joints using
adhesive of polyvinyl chloride family to prevent leakage.
Before drain piping work, remove the pipe cover, hose band, pipe band, and
spacer (cushion). Dispose of the spacer (cushion), as it will not be needed.
Drain hose
is 550 mm long, so that drain piping exit can be moved up. Cut
drain hose
into appropriate length before connecting.
Hose band
Pipe band
Pipe cover
Indoor unit side
Cut within this area
Drain piping side
(Connect drain
pipe
B
)
ø75 mm
5-7 mm
550 mm
430 mm
Ceiling surface
Make sure these
surfaces are ush
with each other
(0-3 mm).
Point for securing grille Point for securing grille
Drain pan
70 mm or more
122 mm
Point for securing grille
Point for securing grille
Enlarged view
Suspension bolt (M10)
Make sure these
surfaces are ush
with each other
(0-3 mm).
Spacer (cushion)
1 2
1 Push
Secure
2 Secure 3 Position in the
center
Unit
Nut with ange (M10)
Special washer (with cushion, 4 pcs)
Special washer
Nut with ange (M10)
Nut (M10)
RG79Y972H01_01En.indd 5 2018/02/27 10:52:17

Other manuals for Mitsubishi Electric MLZ-KP50VF

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric MLZ-KP50VF and is the answer not in the manual?

Mitsubishi Electric MLZ-KP50VF Specifications

General IconGeneral
BrandMitsubishi Electric
ModelMLZ-KP50VF
CategoryAir Conditioner
LanguageEnglish

Related product manuals