EasyManuals Logo

Mitsubishi Electric MS12EN User Manual

Mitsubishi Electric MS12EN
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
4.
FAN
operation
(1) Press POWER ON/OFF button.
(2) Select FAN mode.
(3) Press SET TEMP. button to select the desired temperature.
The indoor fan stops when room temperature is lower than the set temperature
(4) Select the desired fan speed.
Followings are the fan speed in AUTO.
Room temperature minus set temperature
:
4 to
7
deg.("F) or over.....-...-..HI
- -
-
-
-
-
-
-
Room temperature minus set temperature
:
2 to
7
deg.("F)
......-.....-.-.....-MED
-
-
-
-
-
Room temperature minus set temperature
:
-2 to 3 deg.("F)
..-...............
LO
---
Room temperature minus set temperature
:
-2 to 0 deg.("F) or below
..-...
Only indoor fan operates.
Outdoor unit does not operate.
SOFT SLEEP CIRCUIT
5.
TIMER
4
1
.
AUTO STOP operation
AUTO STOP mode has "SOFT SLEEP" circuit which provides comfortable
temperature control for sleeping.
3
(1) Set the TIMER CONTROL to AUTO STOP.
2
4..
(2) Set the time. Time setting is in 1 hour units for up to 12 hours.
8
ti
2
(3) "SOFT SLEEP" circuit operates in COOL mode. By this circuit, system
operates at the set temperature for the first 1 hour. Then, in COOL mode
the set temperature rises by 1 deg. half-hourly to
2
deg. range.
1
In
"I
FEEL CONTROL and DRY mode, the circuit does not operate.
Set temperature
1 Hour
2
Hours
2.
AUTO START operation
(1) Set the TIMER CONTROL button to AUTO START.
(2) Set the time. Time setting is in 1 hour units for up to 12 hours.
NOTE
TIMER setting will be canceled by power failure or breaker functioning.
6.
EMERGENCY-TEST operation
When the remote controller is missing, has failed or the batteries run down, press the emergency run on/off switch on the
front of the indoor unit. The unit will start and the operation lamp will light.
The first 30 min. of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high speed
and the system is in continuous operation.
The thermostat does not operate and the timer is reset to normal.
After 30 min. of test run operation the system shifts to emergency run operation with a set temperature of 75°F in cooling.
The fan shifts to MED speed.
This operation continues until the emergency run
on/off button is pressed or a button on the remote control is pressed, then
normal operation will start.
The coil frost prevention circuit operates in this mode.
EMERGENCY RUN
EMERG~NCY
ON/OFF
button

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric MS12EN and is the answer not in the manual?

Mitsubishi Electric MS12EN Specifications

General IconGeneral
BrandMitsubishi Electric
ModelMS12EN
CategoryAir Conditioner
LanguageEnglish

Related product manuals