315
-
'12 • PAC-T-173
(3) Cooling high pressure control
(a) Purpose:
Prevents anomalous high pressure operation during cooling.
(b) Detector:
Outdoor heat exchanger sensor (TH1)
(c) Detail of operation:
A
B
C
Outdoor heat exchanger temperature (°C)
8rps
(1)
8rps
(1)
0rps
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
After lapse of 20 sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
Notes (1) When the outdoor heat exchanger temperature is in the range of A~CºC, the speed is reduced by 8 rps at each 20 seconds.
(2) When the temperature is 63ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of A~CºC, if the compressor command speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal cooling operation.
(4) Cooling low outdoor temperature protective control
(a) Operating conditions:
When the outdoor air temperature (TH2) is 22ºC or lower continues for 20 seconds while the
compressor command speed is other than 0 rps.
(b) Detail of operation:
1) The lower limit of the compressor command speed is set to 45 (35) rps and even if the speed becomes lower than
45 (35) rps, the speed is kept to 45 (35) rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
2) The upper limit of the compressor command speed is set to 60 (75) rps and even if the calculated result becomes
higher than that after fuzzy calculation, the speed is kept to 60 (75) rps.
Note (1) Values in ( ) are for outdoor air temperature is 22ºC or 25ºC
(2) Cooling overload protective control
(a) Operating conditions:
(b) Detail of operation
(c) Reset conditions:
Outdoor air temperature
Lower limit speed
40 41 46 47
OFF
ON1
ON2
Outdoor air temperature ( )
C
º
1)
2)
Outdoor air temperature(TH2) A B C
TH2
>
=
32ºC
53 58 63
TH2 < 32ºC
51 53 56

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT40VF and is the answer not in the manual?

Mitsubishi Heavy Industries FDT40VF Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT40VF
CategoryAir Conditioner
LanguageEnglish

Related product manuals