316
-
'12 • PAC-T-173
C DA B
OFF
Upper limit 60 rps
Lower limit 45 rps
ON
ON
Upper limit 75 rps
Lower limit 35 rps
Outdoor air temperature C)
First time
Since the seconds
times
9
A
Outdoor air temp. (˚C)
B C D
11 22 25
16 19 25 28
¡
Values of A, B, C, D
(c) Reset conditions:
When either of the following condition is satised
1) The outdoor air temperature (TH2) is D ºC or higher.
2) The compressor command speed is 0 rps.
(5) Heating high pressure control
(a) Purpose:
Prevents anomalous high pressure operation during heating.
(b) Detector:
Indoor heat exchanger thermistor (Th
I
-R)
(c) Detail of operation:
A
B
C D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
After lapse of 10 sec. or over
(3)
lower limit
speed 35rps
(Example) Fuzzy
Notes (1) When the indoor heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 4 rps at each 10seconds.
(2) When the indoor heat exchanger temperature is in the range of C~D ºC, the speed is reduced by 8 rps at each 10 seconds. When the temperature is D ºC
or higher continues for 1 minute, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of A~B ºC, if the compressor command speed is been maintained and the operation has contin
-
ued for more than 10 seconds at the same speed, it returns to the normal heating operation.
(4) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
¡
Temperature list
A B C D
RPSmin < 50
45 52 54.5 61
50
<
=
RPSmin < 115
45 52 57 61
115
<
=
RPSmin < 120
45 ~ 43 52 ~ 50 57 61 ~ 59
120
<
=
RPSmin
43 50 55 59
Unit : ºC
Note (1) RPSmin: The lower one between the outdoor speed and the compressor command speed
(6) Heating overload protective control
(a) Indoor unit side
1) Operating conditions :
2) Detail of operation :
3) Reset conditions :
H
H
ާޓ
ޓ
ޓޓޓޓޓޓި

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT40VF and is the answer not in the manual?

Mitsubishi Heavy Industries FDT40VF Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT40VF
CategoryAir Conditioner
LanguageEnglish

Related product manuals