Page #121 background imageLoading...
Page #121 background image
-
119
-
'19 • SCM-SM-276
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
None
Power source system error
(Power source to indoor unit control PCB)
Stays OFF Stays OFF
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
Are fuses OK
(F1,2)?
YES
YES
Is the
check of resistance between
- of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
NO
(1)
Note (1) for GND
Is DC5V
detected between -
of CNW2?
NO
YES
YES
YES
Is JX1 open?
Is
AC220/240V
detected between
ձ
and
ղ
on the terminal block
of indoor
unit?
NO
YES
NO
Is
AC220/240V
for 1-phase unit detected between
ձ and ղ on the terminal
block of outdoor
unit?
YES
Defective outdoor unit sub
PCB (Noise lter).
Misconnection or breakage
of connecting wires.
Defective indoor unit
control PCB
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor unit
control PCB
Replace.
Open JX1.
Defective indoor unit
control PCB
Replace.
2. Error detection method
3.
Condition of error displayed
4. Presumable cause
Misconnection or breakage of
connecting wires
Blown fuse
Faulty indoor unit control
PCB
Broken harness
Faulty outdoor unit sub PCB
(Noise filter)
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDTC50VH and is the answer not in the manual?

Mitsubishi Heavy Industries FDTC50VH Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDTC50VH
CategoryAir Conditioner
LanguageEnglish

Related product manuals