'19 • SCM-SM-276
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E19
Indoor unit operation check,
drain pump moter check setting error
Keeps ashing
1
-
time ash
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is SW7-1
on the indoor unit control
PCB ON ?
E19 occurs
when the power ON
NO
YES
Defective indoor unit
control PCB (Defective
SW7)
Replace.
Turn SW7-1 on the indoor
unit control PCB OFF and
reset the power.
2. Error detection method
After indoor operation check,
when the communication
between indoor and outdoor
unit is established and SW7-1 is
still kept ON.
3 .
Condition of error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
(Due to forgetting to turn OFF
SW7-1 after indoor operation
check)