68
-
'19 • SCM-SM-276
(3) Defrost operation
(a) Starting conditions
(i)
(ii)
(iii)
(iv)
40
40
finish
Tho-R1
satisfied
The difference between the outdoor air sensor temperature (Tho-A) and outdoor heat
exchanger sensor temperature (Tho-R1) is as following.
2or less
Max. 10 minutes
Defrost operation
Heating operation
Depends on an operation condition, the time can be longer than 7 minutes.
2~7 minutes
Hot keep operation
-20
-20 -15 -10 -5 0 5 10
-15
-10
-5
0
Outdoor air temperature ()
Outdoor heat exchanger temperature ()
Defrost operation
start
Defrost operation start temperature
: After 150 minutes
: Less than 150 minutes
Accumulated compressor operation time
(i)
(ii)
Tho-R
Tho-R1
2
2
13
10
(v)
(i)(ii) (iii) (v)
(b) Ending conditions
Max. 10 minutes
Defrost operation
Heating operation
Depends on an operation condition, the time can be longer than 7 minutes.
2~7 minutes
Hot keep operation
-20
-20 -15 -10 -5 0 5 10
-15
-10
-5
0
Outdoor air temperature ()
Outdoor heat exchanger temperature ()
Defrost operation
start
Defrost operation start temperature
: After 150 minutes
: Less than 150 minutes
Accumulated compressor operation time
(v)
In case satisfied all of following conditions.
• Connect compressor speed 0 rps 10 times or more.
• Satisfy i), ii) and iii) conditions above.
• Outdoor air temperature is 3°C or less.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDTC50VH and is the answer not in the manual?

Mitsubishi Heavy Industries FDTC50VH Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDTC50VH
CategoryAir Conditioner
LanguageEnglish

Related product manuals