22
-
'20 • KX-T-347
(b) Duct type
All models
Color marks
Mark
BK
BL
BR
OR
Color
Black
Blue
Brown
Orange
RD
WH
YE
YE/GN
Red
White
Yellow
YellowGreen
CNM3
WH
C UH
1 3
H M
5 7
L
9
CFi
WH
CNF1
FMi
CNJ
WH
BL
CNS
X1
X6
X3
X2
3
CNJ2
CNR
3
1
WH
1
X4
X5
CNI
BL
BL
WH
CNW1
AC 220240V
CNS2
WH
Tri
TB1
WH
RD
AC 220240V 50Hz
Single-phase
CNW0
WH
CNU
1
3
RD
RD
BL
CNR2
DM
BL
1
M
FS
N
L
1 2 3 4 5 6
Thi-R1
Thi-AThi-R2
1 2 3 4
Thi-R3
5 6 1 2
SW2
SW6
SW5
SW7
SW1 SW3 SW4
F3.15A
F3.15A
YE/GN
Connector for branching
controller of heat recovery
3-pipe systems
M
BK
CNH
BK
CNW2
Earth
1 2
Remote
Thc
TB2
A
B
X
Y
X
Y
1 3
CNK1
WH
CNB
WH
20S
SVH
SVG
SVE
XB1
XB2
XB3
XB4
1
2
3
4
5
+12
CNT2
RD
Signal line
Signal line
between indoor units
Control PCB
SM
19V 24V
1
M
CNN2
BK
CNA2
WH
CNI2
WH
WH
RD
BK
BK
BK
BK
RD
RD
BR
BR
WH
YE
OR
BL
BR
RD
BK
BK
BK
BK
GY
GY
RD
RD
YE
YE
BK
BK
BK
BK
WH
BR
BK
RD
WH
BR
BK
BL
RD
WH
BR
WHYE
YE
WH
OR
RD
RD
WH
BK
BL
RD
Shielded cord
For heat recovery 3-pipe systems
220V 60Hz
YE/GN
Power source
CNA
RD
CNN
YE
BL
between indoor units
Power source line
source line
Power
control
BL
BK
F0.16A
GY
Gray
XR1
XR2
XR3
XR4
XR5Remote operation input
1
2
3
4
5
6
+12
CNT
BL
Operation
Heating
Inspection
Thermo ON
:volt-free contact
Prepare on site
Changing the fan tap
The factory setting of the fan tap is "Standard".
Change the fan tap to "High Speed 1" by using the function
setting of the wired remote control.
CATEGORY
I
U FUNCTION
NUMBER
02
FUNCTION
FAN SPEED SET
SETTING
HIGH SPEED 1
Invalidating the louver button
The factory setting of the louver button is "Valid".
Change the louver button to "Invalid" by using the function
setting of the wired remote control.
CATEGORY
FUNCTIONREMOTE CONTROL FUNCTION
NUMBER
07
FUNCTION
LOUVER SW
SETTING
INVALID
Superlinkspare
JSL1
CNK2
BK
For HA
LED2 LED3
1 1
PIS
Option
2
3
4
1
WH
BK
WH
RD
BK
5
RD
CNG
CNV
Drain pump motor
Fan motor with thermistor
DM
Fuse
Connector
CNA-Z
FMi
F
Description
Item
Capacitor for FMi
CFi
Float switch
FS
Indication lamp Red-Inspection
LED2
Indication lamp Green-Normal operation
LED3
JSL1
Spare Superlink connector change
PIS
Motion sensor
Stepping motor
SM
SW1
SW2
Indoor unit address: tens place
Indoor unit address: ones place
SW3
SW4
Automatic adjustmentFixed previous
Outdoor unit address: tens place
Outdoor unit address: ones place
SW5-1
version of Superlink protocol
for electronic expansion valve
Operation check, Drain pump motor test run
Model capacity setting
SW6
Terminal block Power source)( □ mark
TB1
Terminal block Signal line)( □ mark
TB2
Indoor unit address: hundreds place
SW5-2
SW7-1
Temperature sensor Return air
Temperature sensor Remote control
Thi-A
Thc
Temperature sensor Heat exchanger
Thi-R1,2,3
Transformer
Tri
Closed-end connector
■mark
Relay for FM
X1-3,6
Relay for DM
X4
Relay for LM
X5
WH BK
CNZ CND
1
indicates wiring on site.
2
Use twin core shielded cord
0.75-1.25mm
2
) at signal line between indoor unit
and outdoor unit, and signal line between indoor units.
3
Use twin core cord
0.3mm
2
at remote control line. See spec sheetof remote
control in case that the total length is more than 100m.
4
Do not put signal line and remote control line alongside power source line.
5 Section 1 (※1)
shows electric circuit of motion sensor
option.  
Notes
Meaning of marks
PJC001Z467

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDTQ22KXE6F and is the answer not in the manual?

Mitsubishi Heavy Industries FDTQ22KXE6F Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDTQ22KXE6F
CategoryAir Conditioner
LanguageEnglish

Related product manuals