14
–
'14 • KX-T-222
Model FDU650FKXZE1
・Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (SW8-4 OFF
: 120Pa, SW8-4 ON : 200Pa) , rated E.S.P., and minimum E.S.P. (SW8-4 OFF : 10Pa, SW8-4 ON : 10Pa)
・Characteristic FAN (2) shows air flow vs. E.S.P curve when set fan tap is set Hi with each setting of E.S.P . by remote control.
・External Static Pressure (E.S.P.) can be set by wired remote control.
・You can set required E.S.P. by wired remote control which calculate it with the set air flow rate and pressure loss of the duct connected.
Characteristic FAN (1) Characteristic FAN (2)
0
20
40
60
80
100
120
140
160
180
200
220
240
5 6 7 8 9
Air flow (m
3
/min)
External static pressure (Pa)
0
20
40
60
80
100
120
140
160
180
200
220
240
5 6 7 8 15
Air flow (m
3
/min)
External static pressure (Pa)
Range of approvable air flow
In case actual E.S.P. correcpond setting of E.S.P.
0
20
40
60
80
100
120
140
160
180
200
220
240
7 9 11 13 15
Air flow (m
3
/min)
External static pressure (Pa)
■SW8-4 : OFF (Range of use limitation : Setting 10Pa-120Pa)
Characteristic FAN (1) Characteristic FAN (2)
0
20
40
60
80
100
120
140
160
180
200
220
240
Air flow (m
3
/min)
External static pressure (Pa)
Range of approvable air flow
In case actual E.S.P. correcpond setting of E.S.P.
■SW8-4 : ON (Range of use limitation : Setting 10Pa-200Pa)
4.2 Outdoor air processing unit (FDU-F)
10 11 12 13 14 15
9 10 11 12 13 14 7 159 11 13
Setting 120Pa
Hi
Lo
Setting 60Pa
Hi
Lo
Setting 10Pa
Hi
Lo
Setting 200Pa
Hi
Lo
Setting 120Pa
Hi
Lo
Setting 60Pa
Hi
Lo
Setting 10Pa
Hi
Lo
120Pa
100Pa
80Pa
60Pa
40Pa
20Pa
10Pa
200Pa
180Pa
160Pa
140Pa
120Pa
100Pa
80Pa
60Pa
40Pa
20Pa
10Pa