Page #144 background image
-
142
-
10
Error display :
e28
[Directive remote controller thermistor.]
Indoor unit
Red LED
Green LED
Stays OFF
Keeps flashing
Red LED
Green LED
Stays OFF
Keeps flashing
Outdoor unit
Detectivie remote controller PCB
Replacement (Detective re-
mote thermistor input circuit)
YES
NO
NO
YES
Detective remote controller
thermistor Replacement
Are characteristics of
remote controller therm-
istor OK or is there any
broken wire?
Is the remote controller
thermistor connector co-
nnection OK?
Correction
Temperrature(°C)
0
1
2
4
6
8
10
12
Resistance value (k)
65
62
59
53
48
44
40
36
Temperrature(°C)
14
16
18
20
22
24
26
28
Temperrature(°C)
30
32
34
36
38
40
42
44
Temperrature(°C)
46
48
50
52
54
56
58
60
Resistance value (k)
33
30
27
25
23
21
19
18
Resistance value (k)
16
15
14
13
12
11
9.9
9.2
Resistance value (k)
8.5
7.8
7.3
6.7
6.3
5.8
5.4
5.0
Resistance-temperature characteristic of remote controller thermister

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDURA251 and is the answer not in the manual?

Mitsubishi Heavy Industries FDURA251 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDURA251
CategoryAir Conditioner
LanguageEnglish

Related product manuals