Page #78 background image
4 - 6 4 - 6
MELSEC-Q
4 SETUP AND PROCEDURES BEFORE OPERATION
4.4.2 External wiring
(1) Q64AD-GH
V+
I+
V-
SLD
GND
*1
*4
*2
500k
500k
Shielded
+
-
V+
I+
V-
SLD
Shielded
Signal source 0 to 10V
(a) For voltage input
V+
I+
V-
SLD
GND
*1
*4
*2
250
+
-
500k
500k
Shielded
*3
Signal source 0 to 20V
(b) For current input
*1 Use a 2-core twisted shielded wire for the power wire.
*2 Shows input resistance.
*3 For current input, be sure to connect to (V+) and (I+) terminals.
*4 Be sure to ground the shield wire of each channel.
The SLD terminal can be used when grounding, however it has not been wired inside the board.
Ground it as shown in the diagram shown above or below.
In addition, ground the FG of the power supply module.