!INSTALLATION
I
2.
3.
4.
5.
So
as not to prevent correct ventilation, do not mount the base unit vertically
or horizontally.
Vertical Mounting Horizontal Mounting
(Not allowed) (Not allowed)
The base unit should be mounted on a flat surface
so
as
to
prevent any
strain to the printed circuit boards which could result in damage or incorrect
operation.
Avoid mounting the base unit close to the source of any vibration, such
as
large magnetic contactors and/or large no-fuse breakers. If possible mount
the base unit in a separate panel to the vibration source or mount it as far as
possible from the vibration source.
If any equipment which generates noise or heat is positioned in front of the
PLC
system i.e. the equipment is mounted on the back of the panel door,
allow a minimum clearance
of
100
mW3.94 in. between the front
of
the
PLC
system and such equipment.
,
Panel,
etc.
Door
46