5-3. CORRECTING COOLING AND HEATING CAPACITY
5-3-1. Correcting Changes in Air Conditions
(1)The performance curve charts (Figure 1, 2) show the change ratio of capacity and input (power consumption) according to the
indoor and outdoor temperature condition when defining the rated capacity (total capacity) and rated input under the standard
condition in standard piping length (5m) as “1.0”.
• Standard conditions:
• Use the rated capacity and rated input given in “5-2.”.
• The input is the single value on the side of the outdoor unit; the input on the sides of each indoor unit must be
added to obtain the total input.
(2)The capacity of each indoor unit may be obtained by multiplying the total capacity obtained in (1) by the ratio between the
individual capacity at the rated time and the total capacity at the rated time.
individual capacity at the rated time
Individual capacity under stated conditions = total capacity under the stated conditions o
total capacity at the rated time
Rated cooling capacity
Rated heating capacity
Indoor D.B. 27˚C / W.B. 19˚C
Outdoor D.B. 35˚C
Indoor D.B. 20˚C
Outdoor D.B. 7˚C / W.B. 6˚C
0.4
-5 0 10 20 30 40 46
0.6
0.8
1.0
1.2
1.4
0.6
0.8
1.0
1.2
1.4
22
20
18
16
22
20
18
16
Cooling performance curve
0.6
0.4
0.8
1.0
1.2
1.4
0.4
0.6
0.8
1.0
1.2
1.4
-10-15 -5 0 5 10 15
20
25
15
20
25
15
Heating performance curve
Cooling
Capacity
(ratio)
Cooling
Power
consumption
(ratio)
Heating
Power
consumption
(ratio)
Heating
Capacity
(ratio)
INDOOR
<D.B. :>
INDOOR
<W.B. :>
INDOOR
<W.B. :>
INDOOR
<D.B. :>
Outdoor <D.B. :>
Outdoor <W.B. :>
Figure 2.
PUMY-P100YHM PUMY-P100YHM1 PUMY-P100YHMA(-BS)
PUMY-P125YHM PUMY-P125YHM
1 PUMY-P125YHMA(-BS)
PUMY-P140YHM PUMY-P140YHM
1 PUMY-P140YHMA(-BS)
(3)Capacity correction factor curve
Figure 1.
PUMY-P100YHM PUMY-P100YHM1 PUMY-P100YHMA(-BS)
PUMY-P125YHM PUMY-P125YHM
1 PUMY-P125YHMA(-BS)
PUMY-P140YHM PUMY-P140YHM
1 PUMY-P140YHMA(-BS)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi PUMY-P100YHM and is the answer not in the manual?

Mitsubishi PUMY-P100YHM Specifications

General IconGeneral
BrandMitsubishi
ModelPUMY-P100YHM
CategoryAir Conditioner
LanguageEnglish

Related product manuals