7
4
SPECIFICATIONS
PUMY-P100YHM
(1)
PUMY-P100YHMA
PUMY-P100YHMA-BS
PUMY-P125YHM
(1)
PUMY-P125YHMA
PUMY-P125YHMA-BS
PUMY-P140YHM
(1)
PUMY-P140YHMA
PUMY-P140YHMA-BS
Cooling Capacity
Service Ref.
kW 11.2 14.0 15.5
Heating Capacity kW 12.5 16.0 18.0
Input
(
Cool
)
kW 3.3 4.27 5.32
Input Current
(
Cool
)
A 5.28/5.02/4.84 6.83/6.49/6.26 8.51/8.09/7.80
Input
(
Heat
)
kW 3.63 4.29 5.32
Input Current
(
Heat
)
A 5.81/5.52/5.32 6.87/6.52/6.29 8.51/8.09/7.80
EER
(
Cool
)
3.39 3.28 2.91
COP
(
Heat
)
3.44 3.73 3.38
Connectable indoor units
(
Max.
)
688
Max. Connectable Capacity kW 14.5
(
130%
)
18.2
(
130%
)
20.2
(
130%
)
Power Supply 3 phase
,
50Hz
,
380/400/415V
Breaker Size 16A 16A 16A
Sound level
(
Cool/Heat
)
dB 49 / 51 50 / 52 51 / 53
External finish Munsell 3Y 7.8/1.1
Refrigerant control Linear Expansion Valve
Compressor Hermetic
YHM
(1):ANB33FDEMT, YHMA:ANB33FDKMT
Model
Motor output kW 1.9 2.4 2.9
Starting method Inverter
Crankcase heater W —
Heat exchanger Plate fin coil
(
Anti corrosion fin treatment
)
Fan Fan
(
drive
) %
No. Propeller fan % 2
Fa motor output kW 0.060 + 0.060
Airflow m
3
/min
(
CFM
)
100
(
3
,
530
)
Dimensions
(
HxWxD
)
Wmm
(
in.
)
950
(
37-3/8
)
Dmm
(
in.
)
330+30
(
13+1-3/16
)
Hmm
(
in.
)
1
,
350
(
53-1/8
)
Weight kg
(
lbs
)
140
(
309
)
Refrigerant R410A
Charge kg
(
lbs
)
8.5
(
18.7
)
Protection High pressure protection HP switch
devices Compressor protection Discharge thermo
,
Over current detection
Fan motor protection Overheating/Voltage protection
Oil
(
Model
)
2.3
(
YHM
(1) : MEL56, YHMA:FV50S
)
Total Piping length
(
Max.
)
m
L
120
Farthest m 80
Max. Height difference m 30
Chargeless length m 50
Piping diameter
Gas :mm(in.) 15.88
(
5/8
)
Liquid :mm(in.) 9.52
(
3/8
)
Guranteed operation range
(
cool
)
-5~ 46 DB
(
heat
)
-15~ 15 WB
+3
+3
+3
+3
+3
+3
+1
+2
Rating conditions (JIS B 8616)
Cooling Indoor : D.B. 27: / W.B. 19:
Outdoor : D.B. 35: / W.B. 20:
Heating Indoor : D.B. 20:
Outdoor : D.B. 7: / W.B. 6:
Note.w1. 20m : In case of installing outdoor unit lower than
indoor unit.
w2. 10~46:DB : In case of connecting PKFY-P20/P25 type
indoor unit.
w3. Electrical data is for only outdoor unit.