EasyManuals Logo
Home>National Instruments>I/O Systems>9220

National Instruments 9220 User Manual

National Instruments 9220
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
Caution Do not mix hazardous voltage circuits and
human-accessible circuits on the same module.
Caution Ensure that devices and circuits connected to
the module are properly insulated from human contact.
Caution When module terminals are hazardous
voltage LIVE (>42.4 Vpk/60 VDC), you must ensure
that devices and circuits connected to the module are
properly insulated from human contact. You must use
the NI 9940 connector backshell kit to ensure that the
terminals are not accessible.
Safety Guidelines for Hazardous Locations
The NI 9220 is suitable for use in Class I, Division 2, Groups A,
B, C, D, T4 hazardous locations; Class I, Zone 2, AEx nA IIC T4
and Ex nA IIC T4 hazardous locations; and nonhazardous
locations only. Follow these guidelines if you are installing the
NI 9220 in a potentially explosive environment. Not following
these guidelines may result in serious injury or death.
Caution Do not disconnect I/O-side wires or
connectors unless power has been switched off or the
area is known to be nonhazardous.
6 | ni.com | NI 9220 Getting Started Guide

Other manuals for National Instruments 9220

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments 9220 and is the answer not in the manual?

National Instruments 9220 Specifications

General IconGeneral
BrandNational Instruments
Model9220
CategoryI/O Systems
LanguageEnglish

Related product manuals