NI cDAQ-9181/9184/9188/9191 User Manual
Figure 5-32. Finite Implicit Buffered Pulse Train Generation
Continuous Buffered Implicit Pulse Train Generation
This function generates a continuous train of pulses with variable idle and active times. Instead
of generating a set number of data samples and stopping, a continuous generation continues until
you stop the operation. Each point you write generates a single pulse. All points are generated
back to back to create a user defined pulse train.
Finite Buffered Sample Clocked Pulse Train Generation
This function generates a predetermined number of pulse train updates. Each point you write
defines pulse specifications that are updated with each sample clock. When a sample clock
occurs, the current pulse (idle followed by active) finishes generation and the next pulse updates
with the next sample specifications.
Note When the last sample is generated, the pulse train continues to generate with
these specifications until the task is stopped.
Table 5-7 and Figure 5-33 detail a finite sample clocked generation of three samples where the
pulse specifications from the create channel are two ticks idle, two ticks active, and three ticks
initial delay.
Table 5-7. Finite Buffered Sample Clocked Pulse Train Generation
Sample Idle Ticks Active Ticks
1 3 3
2 2 2
3 3 3
SOURCE
OUT
Counter Armed
2
2 3 42
2

Table of Contents

Other manuals for National Instruments NI cDAQ-9181

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments NI cDAQ-9181 and is the answer not in the manual?

National Instruments NI cDAQ-9181 Specifications

General IconGeneral
BrandNational Instruments
ModelNI cDAQ-9181
CategoryChassis
LanguageEnglish

Related product manuals