• Pre-flashing time:
A manoeuvre warning sign can be activated on the flashing light
before each manoeuvre begins, and the time programmed to 1, 2,
4, 6, 8 and 10 seconds.
• Current sensitivity:
The control unit is equipped with a system which measures the
current absorbed by the two motors used to detect the mechani-
cal stops and any obstacles when the gate is moving. Since the
current absorbed depends on a number of conditions, including
the weight of the gate, friction, wind and variations in voltage, the
cut-in threshold can be changed.
There are 6 levels: 1 is the most sensitive (minimum force), 6 is the
least sensitive (maximum force).
If the “current sensitivity” function (together with oth-
er vital features) is adjusted correctly, the system will
comply with European standards, EN 12453 and EN
12445, which require techniques or devices to be used to
limit force and danger during the functioning of automat-
ic gates and doors are moved.
• Leaf delay:
The delay in starting up the motor of the lower leaf can be pro-
grammed to 5, 10, 20, 30 or 40% of the working time.
7.1) Programming methods
The P1, P2 and P3 buttons are used for all the programming phases, while the 5 Leds (L1, L2…L5) indicate the selected “parameter”.
There are two different programming levels:
• At level 1, the functions can be activated or deactivated. Each Led (L1, L2…L5) corresponds to a function: if the Led is on, the function is
active; if it is off, it is deactivated.
Level one consists in 2 parts which can be selected using the P3 button. The corresponding LED P3 indicates which of the 2 parts has been
selected.
• It is possible to pass to the second level from level one of part one. At this second level the user can choose the parameter relating to the
function. A different value corresponds to each LED which must be associated to the parameter.
Led L1 Led L2 Led L3 Led L4 Led L5
Automatic “Condominium” Pre-flashing Close
Opening delay
closing function after photo
All the functions described in the “Programmable functions” chapter
can be selected by means of a programming phase which terminates
by memorising the choices made.
The control unit therefore has a memory which stores the functions
and parameters relative to the automation process.
7) Programming
Level one (fixed LED P1): part one - (LED P3 off)
Led L1 Led L2 Led L3 Led L4 Led L5
Phototest Electric Lock Resistive STOP Heavy gates Proportional
Open Gate
Level one (fixed LED P1): part two - (LED P3 on)
Led L1 Led L2 Led L3 Led L4 Led L5
Automatic “Condominium” Pre-flashing Close
Opening delay
closing function after photo
Level one (fixed LED P1): part one - (LED P3 off)
Led L1 Led L2 Led L3 Led L4 Led L5
Phototest Electric Lock Resistive STOP Heavy gates Proportional
Open Gate
Level one (fixed LED P1): part two - (LED P3 on)
Second level:
Parameter: Parameter: Parameter: Parameter: Parameter:
Pause Time AUX Input Pre-flashing Current Leaf Delay
Time sensitivity
L1: 5s L1: Open L1: 2s L1: Level 1 L1: 5%
partially type 1 (most sensitive)
L2: 10s L2: Open L2: 4s L2: Level 2 L2: 10%
partially type 2
L3: 20s L3: Open only L3: 6s L3: Level 3 L3: 20%
L4: 40s L4: Close only L4: 8s L4: Level 4 L4: 30%
L5: 80s L5: Photo 2 L5: 10s L5: Level 5 L5: 40%
(least sensitive)
All LEDs off: All LEDs off:
input not used level 6
(max. current
sensitivity)