18
1-2-7 DeviceNet I/O Link Connections
A DeviceNet I/O Link Unit can be used to create an I/O link (remote I/O) of 32
input points and 32 output points with a DeviceNet master, i.e., the CPM1A oper-
ates as a DeviceNet slave. From the standpoint of the CPM1A CPU Unit, the
area allocated to the DeviceNet I/O Link Unit can be treated just like the area
allocated to an Expansion I/O Unit. The difference is that the bits are not actual
I/O points, but I/O bits in the DeviceNet master.
Up to three DeviceNet I/O Link Units can be connected, for a maximum Device-
Net I/O link capacity of 192 I/O points (96 inputs and 96 outputs).
CPM1A CPU Unit (with
30 or 40 I/O points)
DeviceNet (Master) Unit
CS-series, C200HX/HG/HE(-Z),
CVM1, or CV-series PC
DeviceNet I/O Link Unit
(slave)
DeviceNet slave
DeviceNet slave
DeviceNet transmission path
Remote I/O communications are
possible as a DeviceNet slave
for up to 32 input and 32 output
points for each Unit.
1-2-8 Peripheral Device Connections
CPM1A programs can be created or edited with a Programming Console or a
personal computer running SYSMAC Support Software (SSS).
Programming Consoles A CQM1-PRO01-E or C200H-PRO27-E Programming Console can be con-
nected to the CPM1A as shown in the following diagram.
CQM1-PRO01-E C200H-PRO27-E
C200H-CN222/422
CPM1A CPU Unit
System Configuration
Section 1-2