When C200H-series Basic I/O Units are replaced with CS1-series Basic I/O Units, rewiring is required. The C200H
I/O Terminal Block Conversion Adapter that allows the terminal block of the C200H-series Basic I/O Unit to be
reused for the CS1-series Basic I/O Unit is available. This enables efficient replacement by eliminating rewiring and
wiring check times.
Replacement method
Description
(1) Replacing all
C200H-series Units
with CS1-series Units
Replace all C200H-series Units with
CS1-series Units.
Cons: Rewiring of Basic I/O Units is required.
Reference It takes about 1 hour to rewire all
Basic I/O Units (8 to 10 Units) mounted to a
Backplane.
(2) Using C200H I/O
Terminal Block
Conversion Adapters
Replace all C200H-series Units with
CS1-series Units, and mount the C200H I/O
Terminal Block Conversion Adapters to
CS1-series Units.
Pros: Rewiring of Basic I/O Units is not
required, which reduces replacement
time.
Cons: The installation depth is increased.
For details, refer to the C200H I/O Terminal
Block Conversion Adapter Data Sheet.
(3) Using Conversion
Cables for C200H
High-density I/O Units
Replace C200H-ID215 with CS1W-ID231, and
connect CS1W-ID231 using the same
connecting cables used for C200H-ID215.
In the same way, replace C200H-OD215 with
CS1W-OD231, and connect CS1W-OD231
using the same cable used for C200H-OD215.
Pros: Rewiring of I/O Units is not required,
which reduces replacement time.
Note 1. Depending on the type of Basic I/O Unit, there may be some restrictions (e.g. change in I/O
specifications or wiring) or some models cannot be used.
2. When you reuse a terminal block with wiring, confirm that there is no problem in the terminal block and
wiring conditions.
The screws are securely tightened.
The cables are not damaged.
There is no rust or corrosion.
The terminal block is not damaged. (The terminal block is securely inserted and fixed.)
CPU
PS
PS
CS
1-series Units
CPU
PS
PS
CS1-series Units
Reusing existing
terminal blocks
Reusing existing
terminal blocks
C200H I/O Terminal Block Conversion Adapters (CS1W-AT2□□)
CPU
PS
CS1-series Units
CS1W-ID231
Conversion Cable
XW2Z-S010
Connecting cable that was
connected to C200H-ID215
(reuse)
CS1W-OD231
Conversion
Cable
XW2Z-S011
Connecting cable that was
connected to C200H-OD215
(reuse)

Other manuals for Omron CS1G-CPU42H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CS1G-CPU42H and is the answer not in the manual?

Omron CS1G-CPU42H Specifications

General IconGeneral
BrandOmron
ModelCS1G-CPU42H
CategoryController
LanguageEnglish

Related product manuals