20
< TTL Input Unit >
Corresponding CS-series Unit
No replacement model
TTL Input Unit with connector for 32 inputs. The CS Series does not have the
same type of Unit.
Use C200H-ID501 with CS1 or use the CS1W-ID231 24-VDC Input Unit or
CS1W-MD561 TTL I/O Unit instead.
5 VDC, 3.5 mA, Connector,
32 inputs (Special I/O)
< AC Input Units >
Corresponding CS-series Unit
terminal block for 8 inputs.
Replace this unit with a 100
VAC Input Unit with 16 inputs.
2) Input points (8 points → 16 points)
3) Input circuit specifications
Input impedance
(9.7 kΩ/50 Hz → 10 kΩ/50 Hz)
ON voltage (60 VAC → 65 VAC)
4) Internal current consumption
Terminal block, 8 inputs
100 to 120 VDC/1.5 mA,
Terminal block, 16 inputs
terminal block for 8 inputs.
Replace this unit with a 200
VAC Input Unit with 16 inputs.
2) Input points (8 points → 16 points)
3) Internal current consumption
Terminal block, 8 inputs
Terminal block, 16 inputs
terminal block for 16 inputs.
2) No. of circuits (16 points/common x 1 circuit
→ 8 points/common x 2 circuits)
3) Input circuit specifications
Input impedance
(9.7 kΩ/50 Hz→ 10 kΩ/50 Hz)
ON voltage (60 VAC → 65 VAC)
4) Internal current consumption
Terminal block, 16 inputs,
IA122V: Complying with EC
Directive
100 to 120 VDC/1.5 mA,
Terminal block, 16 inputs
terminal block for 16 inputs.
2) No. of circuits (16 points/common x 1 circuit
→ 8 points/common x 2 circuits)
3) Internal current consumption
Terminal block, 16 inputs,
IA222V: Complying with EC
Terminal block, 16 inputs
< AC/DC Input Units >
Corresponding CS-series Unit
terminal block for 8 inputs.
Replace this unit with a DC
Input Unit with 16 inputs.
*The CS Series does not
have an AC/DC Input Unit. If
this Unit is used with AC
inputs, use this C200H-series
Unit with CS1 or change the
wiring for DC inputs.
2) Input points (8 points → 16 points)
3) Input circuit specifications
Input voltage range
(12 to 24 VAC/VDC → 24 VDC)
Input impedance (2 kΩ → 3.3 kΩ)
ON voltage (10.2 VDC → 14.4 VDC)
OFF voltage (3 VDC → 5 VDC)
4) Internal current consumption
Terminal block, 8 inputs
24 VDC, 7 mA, Terminal block,
16 inputs
terminal block for 16 inputs.
Replace this unit with a DC
Input Unit with 16 inputs.
*The CS Series does not
have an AC/DC Input Unit. If
this Unit is used with AC
inputs, use this C200H-series
Unit with CS1 or change the
2) No. of circuits (16 points/common x 1 circuit
→ 8 points/common x 2 circuits)
3) Input circuit specifications
Input voltage range (24 VAC/VDC → 24 VDC)
Input impedance (3 kΩ→ 3.3 kΩ)
4) Internal power consumption
(5 VDC: 10 mA → 100 mA)
24 VAC/VDC, Terminal block,
16 inputs
24 VDC, 7 mA, Terminal block,
16 inputs