6 - 27
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4 Adjustment Level
6
ins
Process Value Input Shift
Sometimes an error occurs between the process value and the actual temperature. To off-
set this, a compensated value can be obtained by adding an input shift value to the input.
The compensated value is displayed as the process value and used for control. The entire
input range is shifted by a fixed rate. If the input shift value is set to −1°C, control will be per-
formed for a value 1°C lower than the measured temperature.
* The decimal point position depends on the Decimal Point parameter setting.
Related Parameters
Input Type (Initial Setting Level): Page 6-43
inrt
Process Value Slope Coefficient
This parameter sets a factor to apply to the input to compensate the process value. The
resulting value is displayed as the process value and used in control.
rss
Remote SP Input Shift
There must be a remote SP input.
The ST (self-tuning) parameter must be set to OFF
(default: ON).
The Remote SP Enable parameter must be set to
ON (default: OFF).
This parameter sets a compensation value to add to the remote SP input to compensate it.
The compensated value is displayed as the process value and used in control.
* The decimal point position depends on the Decimal Point parameter setting.
Related Parameters
Input Type (Initial Setting Level): Page 6-43
ST (self-tuning) (Initial Setting Level): Page 6-46
Remote SP Enable (Advanced Function Setting Level): Page 6-85
Setting range Unit Default
Temperature input: −199.9 to 999.9 °C or °F0.0
Analog input: −1,999 to 9,999* EU 0
Setting range Default
0.001 to 9.999 1.000
Setting range Unit Default
Temperature input: −199.9 to 999.9 °C or °F0.0
Analog input: −1,999 to 9,999 EU 0