EasyManuals Logo
Home>Omron>Controller>E5*C-B Series

Omron E5*C-B Series User Manual

Omron E5*C-B Series
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #303 background imageLoading...
Page #303 background image
6 - 33
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-4 Adjustment Level
6
mV-e
MV at PV Error
The control must be set to 2-PID control or a
Position-proportional Model must be used.
The MV at Stop and Error Addition parameter must
be ON.
This parameter sets the MV to use when an input error occurs.
Related Parameters
MV at Stop and Error Addition (Advanced Function Setting Level): Page 6-74
Close/Floating (Initial Setting Level): Page 6-59
Direct Setting of Position Proportional MV (Advanced Function Setting Level): Page 6-88
sprt
SP Ramp Set Value
The ST (self-tuning) parameter must be set to OFF
(default: ON).
sprl
SP Ramp Fall Value
These parameters set the rate of change during SP ramp operation. They set the
maximum permissible change width per unit of time as the SP ramp set value and the SP
ramp fall value. The SP ramp function is disabled if this parameter is set to OFF.
For a temperature input, the decimal point positions of the SP ramp set value and SP
ramp fall value depend on the currently selected sensor, and for an analog input they
depend on the Decimal Point parameter.
Related Parameters
ST (self-tuning) (Initial Setting Level): Page 6-46
000
Function
Setting
Control method Setting range Unit Default
Standard control
Close position-proportional control with the Direct Setting
of Position-proportional MV parameter set to ON
5.0 to 105.0 % 0.0
Heating/cooling control 105.0 to 105.0
Floating position-proportional control or the Direct Setting
of Position-proportional MV parameter set to OFF
CLOS, HOLD, or
OPEN
None HOLD
See
See
000
Function
Setting
Parameter Setting range Unit Default
SP Ramp Set Value OFF or 1 to 9,999 EU/s, EU/ min, EU/h OFF
SP Ramp Fall Value SAME (Same as SP ramp
set value), OFF or 1 to 9,999
EU/s, EU/ min, EU/h SAME
See
See

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C-B Series and is the answer not in the manual?

Omron E5*C-B Series Specifications

General IconGeneral
BrandOmron
ModelE5*C-B Series
CategoryController
LanguageEnglish

Related product manuals