6 Parameters
6 - 34
E5@C Digital Temperature Controllers User’s Manual (H174)
ol-h
MV Upper Limit The control must be set to 2-PID control.
The ST parameter must be set to OFF.
A Position-proportional Model must be set to close
control.
ol-l
MV Lower Limit
The MV Upper Limit and MV Lower Limit parameters set the upper and lower limits of the
manipulated variable. When the calculated manipulated variable exceeds the upper or
lower limit value, the upper or lower limit value will be the output level.
MV Upper Limit
MV Lower Limit
The MV for the cooling control output during heating/cooling control is expressed as a
negative value.
Related Parameters
PID ON/OFF (Initial Setting Level): Page 6-45
ST (Initial Setting Level): Page 6-46
Close/Floating (Initial Setting Level): Page 6-59
Function
Setting
Control method Setting range Unit Default
Standard control
Close position-proportional control
MV lower limit + 0.1 to 105.0 % 100.0
Heating/cooling control 0.0 to 105.0
Control method Setting range Unit Default
Standard control
Close position-proportional control
5.0 to MV upper limit 0.1 % 0.0
Heating/cooling control 105.0 to 0.0 100.0
See
See

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5*C-B Series and is the answer not in the manual?

Omron E5*C-B Series Specifications

General IconGeneral
BrandOmron
ModelE5*C-B Series
CategoryController
LanguageEnglish

Related product manuals