6 - 63
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
init
Parameter Initialization
This parameter returns all parameter settings to their defaults.
After the initialization, the set value automatically turns OFF.
mspu
Number of Multi-SP Points
The Digital Controller must not have event inputs
or the Event Input Assignment 1 to Event Input
Assignment 6 parameters must not be set to
“Multi-SP No. switching bit 0” to “Multi-SP No.
switching bit 2.”
This parameter sets the number of Multi-SP points that will be used with key operations
(none or 2 to 8).
spru
SP Ramp Time Unit The ST parameter must be set to OFF.
This parameter sets the time unit for the rate of change during SP ramp operation.
Related Parameters
Ramp SP Monitor (Operation Level): 6-10
SP Ramp Set Value and SP Ramp Fall Value (Adjustment Level): Page 6-33
Function
Setting
Setting range Default
off: Initialization is not executed. off
fact: Initializes to the factory settings described in the manual.
Function
Setting
Setting range Default
OFF, 2 to 8 OFF
Function
Setting
Setting range Default
s: EU/s, m: EU/min, h: EU/h m
See
See