6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-8 Advanced Function Setting Level
6
sb1n
Auxiliary Output 1 Open in Alarm Auxiliary output 1 must be assigned.
sb2n
Auxiliary Output 2 Open in Alarm Auxiliary output 2 must be assigned.
sb3n
Auxiliary Output 3 Open in Alarm Auxiliary output 3 must be assigned.
sb4n
Auxiliary Output 4 Open in Alarm Auxiliary output 4 must be assigned.
• This parameter sets the output status of auxiliary outputs 1 to 4.
• When Close in Alarm is set, the status of the auxiliary output function is output
unchanged. When Open in Alarm is set, the status of the auxiliary output function is
reversed before being output. The following table shows the relationship between the
auxiliary output function, auxiliary output, and operation displays (SUB1 to SUB4).
Related Parameters
Auxiliary Output 1 to 4 Assignment (Advanced Function Setting Level): Page 6-82
hbu
HB ON/OFF
HB and HS alarms must be supported.
A Control Output Assignment or Auxiliary Output
Assignment must be set to a heater alarm or heater
burnout alarm.
• Set to use the heater burnout alarm.
Auxiliary output
function
Auxiliary output
Operation display
(SUB1 to SUB4)
Close in
Alarm
ON ON Lit
OFF OFF Not lit
Open in
Alarm
ON OFF Lit
OFF ON Not lit
Setting range Default
n-o: Close in alarm, n-c: Open in alarm n-o
Setting range Default
on: Enabled, off: Disabled on