6 Parameters
6 - 66
E5@C Digital Temperature Controllers User’s Manual (H174)
hbl
Heater Burnout Latch
HB and HS alarms must be supported.
The HB ON/OFF parameter must be set to ON.
When this parameter is set to ON, the heater burnout alarm is held until either of the
following conditions is satisfied.
a Heater burnout detection is set to 0.0 A.
b The power is cycled.
c The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d The latch is cancelled by an event input.
(Event Input Assignment 1 to Event Input Assignment 6 = LAT: Alarm Latch
Cancel)
Output is turned OFF when switching to the Initial Setting Level.
Related Parameters
Heater Burnout Detection 1 (Adjustment Level): Page 6-22
Heater Burnout Detection 2 (Adjustment Level): Page 6-23
Event Input Assignment 1 to 6 (Initial Setting Level): Page 6-57
HB ON/OFF (Advanced Function Setting Level): Page 6-65
PF Setting (Advanced Function Setting Level): Page 6-90
hbh
Heater Burnout Hysteresis
The HB ON/OFF parameter must be set to ON. The
Heater Burnout Latch parameter must be set to
OFF.
HB and HS alarms must be supported.
This parameter sets hysteresis for heater burnout detection.
Related Parameters
HB ON/OFF (Advanced Function Setting Level): Page 6-65
Function
Setting
Setting range Default
on: Enabled, off: Disabled off
See
See
Function
Setting
Setting range Unit Default
0.1 to 50.0 A 0.1
See
See