6 Parameters
6 - 84
E5@C Digital Temperature Controllers User’s Manual (H174)
This parameter sets whether the set point that triggers the alarm is the ramp SP or target SP.
t-u
Soak Time Unit
The Program Pattern parameter must not be set to
OFF.
• Set the soak time unit for the simple program function.
Related Parameters
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Program Pattern (Initial Setting Level): Page 6-47
alsp
Alarm SP Selection
Alarm 1 to alarm 4 must be assigned.
The SP Ramp Set Value parameter must not be set
to OFF and the SP Ramp Fall Value parameter must
not be set to SAME or OFF. The ST parameter must
be set to OFF.
The alarm type must be set to 1, 2, 3, 4, 5, 6, 7, 14,
15, 18, or 19.
Related Parameters
SP Ramp Set Value and SP Ramp Fall Value (Adjustment Level): Page 6-33
ST (Self-tuning) (Initial Setting Level): Page 6-46
Setting
* You can select seconds only for the E5DC, E5DC-B and E5GC. (The E5DC must be
manufactured in July 2014 or later (version 2.2 or higher).)
Setting range Default
s: Seconds,* m: Minutes, h: Hours m
Setting range Default
sp-m: Ramp SP, sp: SP sp-m