A - 17
A Appendices
Digital Temperature Controllers (Simple Type) User’s Manual (H211)
A-5 Parameter Operation Lists
A
A-5-4 Manual Control Level
Parameters Characters Setting (monitor) value Display Default Unit
Manual MV −5.0 to 105.0 (standard)
−105.0 to 105.0 (heating/cooling)
0.0 %
A-5-5 Advanced Function Setting Level
Parameters Characters Setting (monitor) value Display Default Unit
Parameter Initialization init OFF, FACT off, fact OFF None
Number of Multi-SP
Points
mspu OFF(1), 2 to 8 off, 2 to 8 OFF None
SP Ramp Time Unit spru S: EU/second
M: EU/minute
H: EU/hour
s, m, h M None
Standby Sequence
Reset
rest Condition A, condition B a, b Condition A None
Auxiliary Output 1
Open in Alarm
sb1n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
Auxiliary Output 2
Open in Alarm
sb2n N-O: Close in alarm
N-C: Open in alarm
n-o, n-c N-O None
HB ON/OFF hbu OFF, ON off, on ON None
Heater Burnout Latch hbl OFF, ON off, on OFF None
Heater Burnout
Hysteresis
hbh 0.1 to 50.0 0.1 A
ST Stable Range st-b 0.1 to 999.9 15.0 °C or °F
α alfa 0.00 to 1.00 0.65 None
Integral/Derivative
Time Unit
tidu 1, 0.1 1, 0.1 1 Second
Input Digital Filter inf 0.0 to 999.9 0.0 Second
Moving Average Count mav OFF, 2, 4, 8, 16, or 32 OFF Times
MV Display o-dp OFF, ON off, on OFF None
Automatic Display
Return Time
ret OFF, 1 to 99 off, 1 to 99 OFF Second
Alarm 1 Latch a1lt OFF, ON off, on OFF None
Alarm 2 Latch a2lt OFF, ON off, on OFF None
Alarm 3 Latch a3lt OFF, ON off, on OFF None
Alarm 4 Latch a4lt OFF, ON off, on OFF None
Move to Protect Level
Time
prlt 1 to 30 3 Second
Cold Junction
Compensation Method
cjc OFF, ON off, on ON None
Alarm 1 ON Delay a1on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 2 ON Delay a2on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 3 ON Delay a3on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 4 ON Delay a4on 0 to 999 (0: ON delay disabled) 0 Second
Alarm 1 OFF Delay a1of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 2 OFF Delay a2of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 3 OFF Delay a3of 0 to 999 (0: OFF delay disabled) 0 Second
Alarm 4 OFF Delay a4of 0 to 999 (0: OFF delay disabled) 0 Second
Auto/Manual Select
Addition
amad OFF, ON off, on OFF None
Manual Output Method mant HOLD or INIT hold, init HOLD None
Manual MV Initial Value mani
−5.0 to 105.0 for standard control
−105.0 to 105.0 for heating/cooling control
0.0 %
HS Alarm Use hsu OFF, ON off, on ON None
HS Alarm Latch hsl OFF, ON off, on OFF None
HS Alarm Hysteresis hsh 0.1 to 50.0 0.1 A
LBA Detection Time lba 0 to 9999 (0: LBA function disabled) 0 Second