Com Data
SECTION 3 Communications Data for CompoWay/F and SYSWAY
3-14
Note 1. Not displayed on the Controller display.
Note 2. The parameter will not be shown on the Controller display when alarm 3 is not assigned to an
output.
Note 3. After communications parameters have been changed, they are enabled by resetting the
Controller.
Note 4. The setting (monitor) range depends on the “transfer output type” setting. (See the setting data
list for details.)
Note 5. The program end output can be set when the “program pattern” is not set to 0 (OFF).
Note 6. Program start can be set when the “program pattern” is not set to 0 (OFF).
Note 7. The logic is switched only in the MB command (SYSWAY). The logic of CompoWay/F operation
command code 00 (communications writing) is not influenced.
Vari-
able
type
Ad-
dress
Parameter name Setting (monitor) value Level
C3 004C Protocol Setting
(See note 3.)
H'00000000 (0): CompoWay/F (SYSWAY)
H'00000001 (1): Modbus
Commu-
nications
setting
C3 004D Send data wait time
(See note 3.)
H'00000000 to H'00000063 (0 to 99)
C3 004E Control output 1
assignment
When control output 1 is a linear output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
When control output 1 is a pulse output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 5.)
Advanced
function
setting
C3 004F Control output 2
assignment
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 5.)
C3 0050 Alarm 1 assignment H'00000000 to H'00000006 (0 to 6)
* Same settings as control output 2 assignments
C3 0051 Alarm 2 assignment H'00000000 to H'00000006 (0 to 6)
* Same settings as control output 2 assignments
C3 0052 Display character
switch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 0053 Program pattern H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
Initial set-
ting
C3 0054 Soak time units H'00000000 (0): Minutes
H'00000001 (1): Hours
Advanced
function
setting
C3 0055 Alarm SP selection H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point