5.4 Detailed Description of the Services
5-15
(2) Response Code
Normal Completion
Error Occurred
(3) Example Command and Response
The following example shows the command/response for a Stop
command. (In this case, the slave address is H’01.)
Stop command (command code: 01; related information: 01)
Address: H’0000 (fixed)
Write data: H’0101 (Run/Stop, Stop command)
Function
code
Error code Name Description
H'06 --- Normal completion No errors were
found.
Function
code
Error code Name Description
H'86 H'02 Variable address
error
The write variable address was not
“0000.
H'03 Variable data error The write data is incorrect.
Command code or related information
are incorrect.
H'04 Operation error The Controller cannot write the data in
its present operating status.
The “communications writing” param-
eter is set to “OFF” (disabled). The
command is received regardless of
the “communications writing” parame-
ter setting (ON/OFF).
Processing could not be performed.
For details, see (4) Operation Com-
mands and Precautions below.
01 06 00 00 01 01 49 9A(CRC-16)
01 06 00 00 01 01 49 9A(CRC-16)
Command:
Response:

Table of Contents

Other manuals for Omron E5CN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CN and is the answer not in the manual?

Omron E5CN Specifications

General IconGeneral
BrandOmron
ModelE5CN
CategoryTemperature Controller
LanguageEnglish

Related product manuals