129
Advanced Function Setting Level Section 5-7
5-7 Advanced Function Setting Level
The advanced function setting level is used for optimizing Controller perfor-
mance. To move to this level, input the password (“−169”) from the initial set-
ting level.
To be able to enter the password, the “initial setting/communications protect”
parameter in the protect level must be set to 0.
• The parameters in this level can be used when the “initial setting/commu-
nications protect” parameter is set to 0.
• To switch between setting levels, press the O key.
• To change set values, press the U and D keys.
Password input
set value −169
Control in progres
Control stopped
Operation
Level
Initial Setting
Level
Control stops.
Communi-
cations
Setting
Level
Adjustment
Level
Power ON
Advanced Function
Setting Level
25
100
C
Press the O Key
for at least 1 s.
Press the
O Key less than 1 s.
Press the
O Key
for at
least 3 s.
Press the O Key for at
least 3 s.
Press the
O Key for less than 1 s.
Press the O Key
for at least 1 s.