H3G
H3G
317
Characteristics
Accuracy of operating time
!
2% max.
Setting error
!
10% max.
Influence of voltage
!
2% max.
Influence of temperature
!
5% max.
Insulation resistance 100 M
$
min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts, and
between contact-carrying and control circuit, and between contacts of different poles)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance Destruction: 1,000 m/s
2
(approx. 100G)
Malfunction: 100 m/s
2
(approx. 10G)
Ambient temperature Operating: --10
"
Cto55
"
C
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 10,000,000 operations min.
Electrical: See
“Engineering Data.”
Approved standards UL (File No. E41515)
CSA (File No. LR22310) Input: 100/110/120, 200/220/240 VAC (50/60 Hz)
Output: H3G-8A: 7 A at 125, 250 VAC (resistive load)
H3G-8C: 5 A at 125, 250 VAC (resistive load)
SEV
Weight Approx. 55 g
Engineering Data
H3G-8A
Switching operations (x 10 )
3
Load current (A)
H3G-8C
Switching operations (x 10 )
3
Load current (A)