K3MA-J
10
Operating Procedures
Operations in Run Mode
Levels
“Level” refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram tells how
to move between levels. There are some parameters that are not displayed for certain models.
Level name Function Measurement
Protect Setting lockouts. Continue
Operation Displaying current values, setting/clearing forced-zero function, and
setting OUT 1/2 values.
Continue
Initial setting Making initial settings of input type, scaling, output operating action,
and other parameters.
Stopped
Advanced-function setting Setting average processing, display color settings, and other ad-
vanced-function parameters.
Stopped
Setting and Releasing a
Forced Zero
Setting a Forced Zero
Any reference point can be easily set to zero.
Press the Up Key while the measurement is
being displayed. The displayed value will be
shifted to 0 and measurement will be
continued.
The Z indicator will light when a forced zero
has been set.
The shifted measurement value after a forced
zero has been set will be maintained even
after power is turned OFF.
Releasing a Forced Zero
Press the Up Key for 1 s min. to release the
forced zero. The Z indicator will turn OFF.
If forced-zero protection is turned ON in the
protect level, the Up Key cannot be used to
set a forced zero. Forced-zero protection is
ON in the default settings.
Displayed value
Forced zero input
Z indicator
OFF ON
Measured value
Measured value
after setting
forced zero
Checking the Maximum and Minimum Values
The maximum and minimum values can be displayed by pressing the MAX/MIN Key while
the measurement is being displayed.
The maximum and minimum values can be reset by pressing the MIN/MAX Key for 1 s
min. when the maximum or minimum value is displayed.
Checking and Setting Comparative Set Values (for
Models with the Comparative Output Function)
Each time the Mode Key is pressed when the measurement value, maximum value, or
minimum value is displayed, the comparative values will be displayed in the following
order: OUT1 value (or OUT1 upper-limit value, OUT1 lower-limit 1), OUT 2 value (or OUT
2 upper-limit value, OUT2 lower-limit value 2).
Note: When a comparative value is displayed, it can be changed by pressing the Shift Key
and the Up Key (when key protection is OFF).
Measurement
value
MAX value MIN value
MAX/MIN Key MAX/MIN KeyMAX/MIN Key
Measurement
value
MAX value
MIN value
OUT1
upper-limit
value
OUT1 value OUT2 value
OUT1
lower-limit
value
OUT2
upper-limit
value
OUT2
lower-limit
value
Mode Key Mode Key Mode Key Mode Key Mode Key