Electrical Installation
3
3.5 Control Circuit Wiring
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 85
3.5 Control Circuit Wiring
This section gives information about wiring the control circuit.
Control Circuit Connection Diagram
Wire the drive control circuit as shown in Figure 3.33.
Figure 3.33 Control Circuit Connection Diagram
*1 To operate the control circuit while the main circuit power supply is OFF, connect a 24 V power supply unit
(option).
*2 Install a wire jumper between terminals DIC-D24V-D0V to select the type of the power supply for MFDI
(sinking/sourcing mode or internal/external power supply).
NOTICE: Do not close the circuit between terminals D24V and D0V. Failure to obey will cause damage to the drive.
Sinking Mode: Install a jumper between terminals DIC and D24V.