Output
Lead Markings: Generators are marked Tl, T2, etc.
These
identifying
marks also
appear
on the
wiring
diagram.
Voltage
Selection on Reconnectible Single
Phase
Genera-
tors:
These
models are reconnectible for use as a 120/240
volt
3
wire;
a 120
volt
2
wire
or 240volt 2
wire
power source
(Figure
12).
Load
Connections: Refer to the
figure
which
illustrates
the load connections for the output shown on your
set's
nameplate.
CAUTION
Do
not use
existing neoprene impeller
water pump
lor hot
water side
ol
cooling
system. Heat
or
soluble
oil (in
many rust inhibitors
and
anti-lreezes) will damage
the
impeller. Always connect
the neoprene impeller pump
to the
cold water side.
Use
a centrifugal metal impeller water pump (Onan #132-0110
or equal)
in the hot
water side. Drive
it
with
a
belt from
the set's power take-oll.
Spec
A through C: Use an expansion tank in the hot water
side.
Delta
Generator: Generator lead To is the generator center
tap between Tl and T2. The To lead is normally not
grounded but can be grounded if required (Figure
12-B).
Single
phase
power at center tapped leg available up to
2/3 of
full
rated three
phase
power.
Discharged
water
leaves
at
heat
exchanger and then to
exhaust system water
inlet.
Supply
line
connections are
the
same
as standard system (Figure 13). Refer to the
instructions
for water supply
line
in this section.
Fill
closed
cooling
systems
with
clean, alkali-free water,
to
the proper
level.
Add an approved rust
inhibitor
to the
coolant.
If the coolant is anti-freeze, test it periodically.
HEAT
EXCHANGER
COOLING
(Optional).
This
is a closed
cooling
system commonly referred to as
fresh
water
cooling.
Water circulated through the engine is
termed
fresh . water, hot water, jacketed water, etc. Water
circulated
through the
heat
exchanger
only
is called raw
water, sea water,
cold
water, discharged water, etc. This
system
(with
anti-freeze coolant) is recommended where
freezing
hazards
exist or where the owner wants to prevent
salt water problems.
Two
conditions
prevail:
(1) Factoiy installed
heat
exchanger,
and (2) Customer installed Onan
heat
exchanger kit. Get
details
from
Onan.
Install
a new zinc
"pencil"
(Figure 13)
which
screws
into
fresh
water outlet end of
heat
exchanger, every two months
or
as inspection dictates.
l^^y^QlJ^jj
Use
high temperature cut-oil switch
in
overheating.
1
the hot
water side
to
protect unit Irom
14

Questions and Answers: