8.5. Operation Control
8.5.1. Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
8.5.2. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and
restart automatically.
Time Delay Safety Control is activated before the compressor restart.
T = Intake air temperature - Indoor heat exchanger temperature
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
19
CS-A18DKD CU-A18DKD / CS-A24DKD CU-A24DKD

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A24DKD and is the answer not in the manual?

Panasonic CS-A24DKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-A24DKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals