54
12.4 Automatic Operation
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit starts to operate at determined operation mode, until it is switched off using remote control, with
the setting temperature as shown in table below.
Setting Temperature (Standard)
Cooling Operation 25°C
Soft Dry Operation 22°C
Heating Operation 21°C
• Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches
to set temperature and compressor off time is over 7 minutes 30 seconds continuously.
* The present operation mode will be continued, if the room temperature does not reach to set temperature
(Compressor keeps running) eventhough after 1 hour from automatic operation mode started.
Standard for Determining Operation Mode
2nd Judgement onwards
Next Mode
Present Mode Judgement
Cooling Soft Dry Heating
Cooling
23°C
Heating
Cooling
O
(Judgement:
23°C & Above)
Not Applicable
O
(Judgement:
Below 23°C)
Soft Dry
20°C
Heating
Soft Dry
Not Applicable
O
(Judgement:
20°C & Above)
O
(Judgement:
Below 20°C)
Cooling
25°C
Heating
Heating
O
(Judgement:
25°C & Above)
Not Applicable
O
(Judgement:
Below 25°C)
• Automatic Set Temperature
For each operation, set temperature will automatically set as shown below.
• The setting temperature for all the operations can be changed one level up or one level down from the standard
temperature as shown in below table by pressing on the temperature up or temperature down button at remote
control.
Hi (Standard) Lo
Operation
(+2°C) (±0°C) (-2°C)
Cooling 27°C 25°C 23°C
Soft Dry 24°C 22°C 20°C
Heating 23°C 21°C 19°C
Cooling Operation
Soft Dry Operation
↑
Intake Air
Temperature
23°C
20°C
Heating Operation