Page 28 Issue 2 22/4/98 MPC2000D
COMMUNICATION SETTINGS
Drive Number 1 - 320 0
Baud Rate 110,300,1200,2400,4800,9600,19200 9600
Serial Link No. 1 - 33 33
Fast Scan Anal 1 0 - 201 0
Fast Scan Anal 2 0 - 201 1
Fast Scan Anal 3 0 - 201 2
Fast Scan Update 0 - 30s 0
SYSTEM PARAMETER SETTINGS
Line Voltage 100v-22kv 415v
VT Primary Not Connected, 100v-22kv Not Connected
VT Secondary " " , 95-660v " "
Motor FLC 1-2500A 100A
CT Primary 1-2500A 100A
E/F CT Primary 1-2500A 100A
Earth fault Alarm 1-100% Inom 5% Inom
" " " Delay 1-60 Sec 10 sec
Earth Fault Trip 1-100% Inom 10% Inom
" " " Delay 0-2 Sec 0.5 Sec
Current Inhibit off, 400-1000% FLC off
Start/Stop Signal Momentary, Maintained Momentary
Starting Method DOL,Star/Delta,Reversing DOLNR
2 Speed,Circuit Breaker
Max Time in Star 1-60 Sec 10 Sec
Transition Time 0.05-2.0 Sec 0.2 Sec
Star to Delta at 40-200% FLC 150% FLC
Low Speed FLC 1-2000A 10A
Low Speed t6X 0.5-120Sec 10 Sec
Designate Aux 1 Alarm,Contactor A, Contactor B, Run Alarm
Aux 1 Delay 0-120 Sec 0
Designate Aux 2 Trip, Trip Fail Safe, Contactor A, Trip
Contactor B
Aux 2 Delay 0-120 Sec 0
Protection Only Yes, No No
VOLTAGE SETTINGS
Undervoltage Setting 50-95% 80%
Undervoltage Delay 0.2-10 Sec 5 Sec
Undervoltage Restart Yes,No No
Undervoltage Restart Delay 0.2-120 Seconds
Overvoltage Alarm 100-120% 115%
Overvoltage Trip 100-120% 120%
Overvoltage Trip Delay 1-100 Sec 1 Sec
CURRENT SETTINGS
Maximum Start Time 1-250 Sec 10 Sec
Number of starts 1-10 10
Start Period 1-60 Min 30 Min
Start Inhibit Time 1-60 Min 30 Min
Undercurrent Alarm 10-90% FLC 50%
Undercurrent Alarm Delay 1-60 Sec 2 Sec
Undercurrent Trip 10-90% FLC 40$
Undercurrent Trip Delay 1-60 Sec 5 Sec
Load Increase Alarm 60-150% FLC 120%
Low Set Overcurrent 100-500% FLC 400%
Low Set Overcurrent Delay 0.5-10 Sec 2.0 Sec
High Set Overcurrent 400-1200% FLC 800%
High Set Overcurrent Delay Inst-4 Sec Inst
Overload Setting 60-130% FLC 105%
Thermal Capacity Alarm 50-99% 80%
t6x Time 0.5-120 Sec 10 Sec
Hot/Cold Ratio 20-100% 50%
Cool Time Factor 1-15 5
Stall Time Factor 20-100% 50
Overload reset Method Auto,Hand Hand
Unbalance Current 10-40% 15%
Current Unbalance Maximum Time 20-120 Sec 30 Sec