14/1/98 Page 7 Issue H
5.1.1. Mode 1 Display.
The following subset of parameters are available for viewing and are accessed using the
<SELECT/RESET> push-button in a cyclic manner. Pressing for longer than 1 second returns to the
start of the cycle. Parameters available are either actual real-time running values or memorised
values as follows:
Data Displayed (ALL CURRENTS
IN PRIMARY AMPS)
LED's Illuminated
P&B (Relay Manufacturer)
Actual line current L1 L1 (Green)
Actual line current L2 L2 (Green)
Actual line current L3 L3 (Green)
Actual Earth Fault Current E (Green)
Stored Max Starting Current L1 * L1 (Green - Red-Alternating)
Stored Max Starting Current L2 * L2 (Green - Red-Alternating)
Stored Max Starting Current L3 * L3 (Green - Red-Alternating)
Earth Fault Current * E (Green - Flashing)
Actual Load Current (%) * L1, L2 & L3 (Green)
Actual Thermal Capacity (%) L1, L2 & L3 (Green - Flashing)
Actual Unbalance (%)* I2
Total Number of Starts OPS/HR (Green)
Total Hours Run OPS/HR (Green - Flashing)
Latest Start Time in seconds ST (Green)
Relay Address For Communications RS (Green)
t6x Setting 1 (Green)
Full Load Current (I FLC) 1 (Green - Flashing)
Table 1 - Display mode (1)
In addition to the above, when the motor is starting the S/R LED indicates Green-Flashing and when
the motor is running the S/R LED indicates Green-Steady. The value of motor load is held after a trip
and updated when the next start is detected. Total hours run is the total time the relay has detected a
running motor. When the kA illuminates the display value is multiplied by 1000, e.g. to read line
current in kA or hours run in 1000’s of hours.
* FOLLOWING A RELAY TRIP THIS VALUE IS THE STORED PRE-TRIP FAULT VALUE. TO
RESET THE RELAY FOLLOWING A TRIP AND CANCEL THE STORED TRIP
VALUES,(EXCEPT THE STORED MAX/STARTING CURRENT L1, L2 AND L3) PRESS THE
<SELECT/RESET> BUTTON FOR MORE THAN 3 SECONDS, OR RE-START THE MOTOR.