1 INFORMATION ON THIS DOCUMENT
1.1 Function
The present instruction manual provides information on installation, connection and
safe use for the following articles: CS AR-08••••
1.2 Target audience
The operations described in this instruction manual must be carried out by qualified
personnel only, who are fully capable of understanding them, and with the technical
qualifications required for operating the machines and plants in which the safety de-
vices are to be installed.
1.3 Application field
These instructions apply exclusively to the products listed in paragraph Function, and
their accessories.
1.4 Original instructions
The Italian language version is the original set of instructions for the device. Versions
provided in other languages are translations of the original instructions.
2 SYMBOLS USED
This symbol indicates any relevant additional information
Attention: Any failure to observe this warning note can cause damage or mal-
function, including possible loss of the safety function.
3 DESCRIPTION
3.1 Device description
The safety device described in this manual is defined according to the Machinery
Directive 2006/42/EC as logic component for safety functions.
The safety modules to which these usage instructions refer, are devices specifically
designed and manufactured to be applied on industrial machines, in order to realize
emergency stop and end position monitoring circuits for movable guards. With these
modules, it is possible to create systems with safety category up to SIL CL 3 acc. to
EN 62061 and up to category 4 / PL e acc. to EN ISO 13849-1.
3.2 Device functions
- Safety function performed by the module: upon opening of at least one channel,
the safety relays must open their output contacts within the defined reaction time.
The safety outputs of the module are enabled only if the channels CH1 and CH2 are
consistently closed and after activating the START signal.
- Input with 1 or 2 channels.
- The SIL 3 / PL e safety function is only available with the two redundant inputs
configuration.
- Choice between automatic start, manual start or monitored start.
With reference to the "automatic" operating mode, consider RES 1.2.3 of the
Machinery Directive 2006/42/EC: "For machinery functioning in automatic mode, the
starting of the machinery, restarting after a stoppage, or a change in operating condi-
tions may be possible without intervention, provided this does not lead to a hazardous
situation".
- Connection of input channels of opposite potentials.
- Can be connected to semiconductor outputs (e.g. light barriers), to electromechani-
cal contacts or to magnetic safety sensors.
- Short circuit detection function of the control elements by means of safety system
with self-monitoring and redundancy.
- LED indicators for switching state of the channels CH1, CH2 and for the power sup-
ply voltage.
- Short circuit detection function of the control elements by means of safety system
with self-monitoring and redundancy.
- Snap-mounting on DIN rails.
3.3 Intended use of the device
- The device described in this manual is designed to be applied on industrial machines.
- The direct sale of this device to the public is prohibited. Installation and use must be
carried out by qualified personnel only.
- The use of the device for purposes other than those specified in this manual is
prohibited.
- Any use other than as expressly specified in this manual shall be considered unin-
tended by the manufacturer.
- Also considered unintended use:
a) using the device after having made structural, technical, or electrical modifications
to it;
b) using the product in a field of application other than as described in paragraph
TECHNICAL DATA.
4 OPERATION
4.1 Function diagrams
Automatic
start:
A1/A2
S11/S12 (+/S12)
S21/S22 (+/S52)
13/14, 23/24
t
C
t
A
t
R1
t
R1
t
C
t
A
t
R
t
A
Monitored
start:
A1/A2
S33/S34 (START)
13/14, 23/24
t
A
t
R1
t
R1
t
A
t
R
t
MIN
t
A
S11/S12 (+/S12)
S21/S22 (+/S52)
Manual start:
A1/A2
S33/S34 (START)
13/14, 23/24
t
A
t
R1
t
R1
t
A
t
R
t
MIN
S11/S12 (+/S12)
S21/S22 (+/S52)
Legend:
t
MIN
: Min. duration of start impulse
t
C
: Simultaneity time
t
A
: Response time
t
R1
: Release time
t
R
: Release time in absence of power
supply
Notes: The configurations with one channel are obtained taking into consideration the
CH1 input only. In this case it is necessary to consider time t
R1
referred to input CH1,
time t
R
referred to the supply, time t
A
referred to input CH1 and to the start, and time
t
MIN
referred to the start.
4.2 Wiring diagrams
Emergency stop circuits
Input configuration with manual start
1 channel (SIL 1 - PL c - Cat. 1)
Input configuration with manual start
2 channels (SIL 3 - PL e - Cat. 4)
S33
S21 S22
S35
S34
CS AR-08
A2
S31
S11
S12
A1
L / +
N / -
S33
S21 S22
S35
S34
CS AR-08
A2
S31
S11
S12
A1
N / -
L / +
Semiconductor outputs (example: light barriers)
(for articles CS AR-08024 only)
Input configuration with manual start
1 channel (SIL 1 - PL c - Cat. 1)
Input configuration with manual start
2 channels (SIL 3 - PL e - Cat. 4)
24 VDC
+
-
OSSD
S52
S33
S21 S22
S35
S34
S12
CS AR-08
A1
A2
24 VDC
+
-
S52
S33
S21 S22
S35
S34
S12
CS AR-08
A1
A2
OSSD1 OSSD2
S34 S34
Automatic start
With regard to the indicated diagrams, short-circuit the S33
and S34 terminals in order to activate the automatic start
module.
S21
S22
S21
S22
S35 S35
Monitored start
With regard to the indicated diagrams, remove the connec-
tion between the S22 and S35 terminals in order to activate
the monitored start module.