1-877-420-1330
Quest 876 Installation, Operation and Maintenance Instructions
4
www.QuestClimate.com
info@QuestClimate.com
1. Intended Application for Quest 876 Dehumidifier
The Quest 876 Dehumidifier is designed to operate in temperatures between 56° and 110°F.
In order to eciently control humidity levels, the area in which the dehumidifier is to be operated must be free of water
intrusion or excessive fresh (outside) air infiltration. Before installing the Quest 876 Dehumidifier, water intrusion and air
infiltration problems should be addressed or noted in calculations.
2. Registrations
The Quest 876 Dehumidifier units conform to unified standards: UL 60335-2-40, CSA 22.2 # 60335-2-40:2012 Ed.
1+4.
US Patent #10,168,058
Patent Pending #7194870
#7246503
3. Specifications @ 80°F/60% RH
Unit: Quest 876
4037600
CFM
1850@0.0”WG
Power (Watts):
5500
Supply voltage:
220-240 VAC -
1 Phase - 60 Hz.
Current Draw (Amps):
24.7
Rated Current Draw (Amps):
(104°F 36%)
31.5
Minimum Circuit Ampacity (MCA):
42.5A
Maximum Overcurrent Protection (MOP):
70A
Energy Factor (L/kWh):
3.1
Operating Temp:
56°F Min - 110°F Max
Water Removal (Pints/Day):
Eciency (Pints/kWh):
876
6.6
Air Filter (MERV-13): (2)
Size: 18" x 20" x 2"
Power Cord:
Cord not provided -
Direct wired only
Electrical Knockout Size
3/4” (1.094” opening)
Drain Connection:
3/4 Threaded NPT
Refrigerant Type:
Refrigerant Amount:
R410A
6lbs 4oz
Dimensions:
Width:
Height:
Length:
Weight:
Unit Shipping
28.9” 36”
33.8” 40”
44.7” 48”
340 lbs 420 lbs
* requires external control not provided
* requires buck/boost transformer
to run on 208V or 277V