17 ESP-LXIVM Controller Troubleshooting Guide
Table of
Contents
Shorted Path (Manual Method) cont.
YES NO
The problem is
upstream between this
point and the controller
Re-connect the 2-wire path
and go to an IVM device
approx. 50% between this
point and the controller.
Disconnect the 2-wire splice
to disconnect the second
half of the 2-wire path.
The problem is downstream
between this point and the
end of the 2-wire path
Re-connect the 2-wire path
and go to an IVM device
approx. 50% between this
point and the end of the
2-wire path. Disconnect the
2-wire splice to disconnect the
second half of the 2-wire path.
Next Page
For video instructions on Automatic Short
Finding Mode, please visit:
www.rainbird.com/esplxivm
NOTE: Once a small section 2-wire path is identified as having an
issue, use “Energize Path for Testing” and Milliamp Meter to track
for a sharp increase in test current before the location of the short.