EasyManuals Logo
Home>Rheem>Air Conditioner>ASL-JEC 18 Seer

Rheem ASL-JEC 18 Seer User Manual

Rheem ASL-JEC 18 Seer
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26
ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
12.7
COMFORT CONTROL
2
SYSTEM™ CONTROL WIRING
AND
CONVENTIONAL THERMOSTAT WIRING
ICC DIAGNOSTIC CODES
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
0 Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to defeat short cycle delay.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to defeat short cycle delay.
Status/Possible Cause – Troubleshooting
Information
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
t - Test Mode The ICC is in TEST mode
10
1
3.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
L
EDs Display
Code Diagnostic Description
S
tatus/Possible Cause – Troubleshooting
Information
0 – Standby
N
o command for unit operation
Normal operation
c
- First Stage Cooling
Unit has received a command for first stage
c
ooling
N
ormal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
o
r minimum run timer.
Wait until unit timer has expired or press the
T
EST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
N
ormal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
M
inimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
10
13.X ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
7-Segment
LEDs Display
Code Diagnostic Description
Status/Possible Cause – Troubleshooting
Information
0 – Standby
No command for unit operation
Normal operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
FLASHING
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to reset timer.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
FLASHING
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h1 - First Stage Heat Pump
Unit has received a command for first stage
heat pump
Normal operation
FLASHING
h1 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
heat pump during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
h2 - Second Stage Heat Pump
Unit has received a command for second
stage heat pump
Normal operation
FLASHING
h2 - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage heat pump during an active anti-short
cycle timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to reset timer.
d - Defrost Active
The unit is undergoing a defrost cycle
Normal operation
t - Test Mode The ICC is in TEST mode
P Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
11
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not
Run)
The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
09 Low Secondary Volts
The secondary voltage at R and C is below
18VAC
Control transformer overloaded
Low line voltage
01 Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
11
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not
Run)
The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
09 Low Secondary Volts
The secondary voltage at R and C is below
18VAC
Control transformer overloaded
Low line voltage
02 High Side Fault
Compressor limit has opened four (4) times
within a call for operation
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
11
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not
Run)
The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
09 Low Secondary Volts
The secondary voltage at R and C is below
18VAC
Control transformer overloaded
Low line voltage
03 Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
11
d1 No Shared Data
ELECTRONICS GROUP TO
DESCRIBE
d3 – Airflow CFM Mismatch
The indoor air mover (air handler/furnace)
cannot supply the required airflow for
proper system operation
Misapplied/wrong indoor air mover – replace
with properly sized air handler/furnace.
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line voltage disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 High Pressure Control Open
The ICC detects the HPC is open.
Reference ICC codes:
21
L21
29
L29
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
L4 – Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the
average run time for each trip is less than 15
seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
05Open Circuit (Compressor will not
Run)
The ICC has received a command for
unit operation but no current is present in
the start and run circuits.
The ICC will attempt to restart the unit
every five (5) minutes for four (4)
attempts. After that, the ICC will attempt
a restart every twenty (20) minutes for up
to four (4) hours.
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
Check for open compressor internal protector
06 Compressor Open Start Circuit
The ICC detects current in the Run circuit
but not in the Start circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
07 Compressor Open Run Circuit
The ICC detects current in the Start circuit
but not in the Run circuit of the compressor
Check for damaged, miswired, or wrong run
capacitor
Check for broken wires, loose connectors, or
miswired compressor
Check compressor windings for continuity
09 Low Secondary Volts
The secondary voltage at R and C is below
18VAC
Control transformer overloaded
Low line voltage
L4 Locked Rotor
The ICC detects four (4) consecutive
protector trips have occurred and the run time
before each trip is less than 15 seconds
Bad run capacitor
Low line voltage
Excessive refrigerant in compressor
Seized bearings in compressor
L
0 7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem ASL-JEC 18 Seer and is the answer not in the manual?

Rheem ASL-JEC 18 Seer Specifications

General IconGeneral
BrandRheem
ModelASL-JEC 18 Seer
CategoryAir Conditioner
LanguageEnglish

Related product manuals