EasyManuals Logo
Home>Rheem>Air Conditioner>ASL-JEC 18 Seer

Rheem ASL-JEC 18 Seer User Manual

Rheem ASL-JEC 18 Seer
33 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
FIGURE 1
DIMENSIONS AND INSTALLATION CLEARANCES
UNIT MODEL NUMBER EXPLANATION
(
-)ASL 036 JEC
E
C = EQUIPPED WITH THE
COMFORT CONTROL
2
SYSTEM™
J
- 208/230-1-60
(
NOMINAL CAPACITY)
024 = 24000 BTU/HR
036 = 36000 BTU/HR
039 = 39000 BTU/HR
048 = 48000 BTU/HR
060 = 60000 BTU/HR
L = DESIGN SERIES (R-410A)
S = 18 SEER
A = REMOTE CONDENSING UNIT
TRADE NAME
A
IR INLETS
(
LOUVERS)
A
LLOW 120 [305 mm]
M
IN. CLEARANCE
3
SIDES
AIR DISCHARGE
ALLOW 600 [1524 mm] CLEARANCE
ALLOW 240 [610 mm]
ACCESS CLEARANCE
ACCESS
PANEL
L
W
H
ALTERNATE HIGH VOLTAGE
CONNECTION (KNOCKOUT)
1
11
/320 [34 mm]
SERVICE
F
ITTINGS
LOW VOLTAGE
CONNECTION
7
/8"
[22 mm]
HIGH VOLTAGE
CONNECTION
1
1
1
/32" [34 mm]
LIQUID LINE
CONNECTION
SERVICE ACCESS
TO ELECTRICAL &
VALVES ALLOW
24" [610 mm]
CLEARANCE
ONE SIDE
2
7
/8" [73 mm] DIA.
ACCESSORY
KNOCKOUTS
VAPOR LINE
CONNECTION
A-00002
BASE PAN
A
LLOW 24" [610 mm]
ACCESS CLEARANCE
ALTERNATE LINE VOLTAGE
ENTRY (KNOCKOUT)
1
11
32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
AIR INLETS
(LOUVERS)
ALLOW 6” [152 mm]
MIN. CLEARANCE
3 SIDES
ACCESS
PANEL
AIR DISCHARGE
ALLOW 60" [1524 mm] CLEARANCE
BOTTOM VIEW SHOWING DRAIN OPENINGS
(\\\\\ SHADED AREAS).
LINE VOLTAGE ENTRY
1
11
32" [34 MM]
CONNECT THE LINE
VOLTAGE CONDUIT TO
THE BOTTOM OF THE
CONTROL BOX
2.3 DIMENSIONS
2.4 ELECTRICAL & PHYSICAL DATA
6
LINE VOLTAGE
ENTRY
7
8" [22 MM]
SERVICE ACCESS
FOR 024 & 036 MODELS
SERVICE ACCESS
FOR 039, 048 & 060 MODELS
LOW LINE
VOLTAGE
7
8"
LOW LINE
VOLTAGE
7
8"
VAPOR LINE
CONNECTION
LIQUID LINE
CONNECTION
SERVICE
FITTING
HIGH LINE
VOLTAGE 1
1
4"
TABLE 1
(-)ASL-JEC ELECTRICAL DATA
Model
Number
RASL-
Phase
Frequency
(Hz)
Voltage
(Volts)
Compressor
Fan
Motor
Full Load
Amperes
(FLA)
Minimum
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Outdoor Coil Weight
Minimum
Amperes
Maximum
Amperes
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s}
Refrig.
Per
Circuit
Oz. [g]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
ELECTRICAL PHYSICAL
Rated Load
Amperes
(RLA)
Locked
Rotor
Amperes
(LRA)
Rev. 2/24/2010
024JEC 1-60-208/230 10.3/10.3 52 0.5 14/14 20/20 20/20 15.8 [1.47] 1 2500 [1038] 144 [4082] 236 [107] 263.5 [119.5]
036JEC 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1 3400 [1321] 150 [4252] 250.5 [113.6] 314.5 [142.7]
039JEC 1-60-208/230 17.9/17.9 96 2.8 26/26 30/30 40/40 23 [2.14] 2 3500 [1321] 268 [7598] 326 [147.9] 345 [156.5]
048JEC 1-60-208/230 26.9/26.9 117 2.8 37/37 45/45 60/60 23 [2.14] 2 3500 [1321] 253 [7173] 326 [147.9] 348 [157.9]
060JEC 1-60-208/230 28.2/28.2 146 2.8 39/39 50/50 60/60 23 [2.14] 2 3500 [1321] 241 [6832] 328 [148.8] 346 [156.9]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem ASL-JEC 18 Seer and is the answer not in the manual?

Rheem ASL-JEC 18 Seer Specifications

General IconGeneral
BrandRheem
ModelASL-JEC 18 Seer
CategoryAir Conditioner
LanguageEnglish

Related product manuals