Air
General Data/Electrical Data
RA13 Series
8
Physical Data
PHYSICAL DATA
Model No. RA1318A RA1324A RA1330A RA1336A RA1342A RA1348A RA1360A
Nominal Tonnage 1.5 2.0 2.5 3.0 3.5 4.0 5.0
Valve Connections
Liquid Line O.D. – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Suction Line O.D. – in. 3/4 3/4 3/4 3/4 7/8 7/8 7/8
Refrigerant (R410A) furnished oz.¹ 56 66 78 92 111 112 154
Compressor Type Scroll
Outdoor Coil
Net face area – Outer Coil 5.9 9.1 9.1 12.1 14.2 14.8 18.8
Net face area – Inner Coil
Tube diameter – in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Number of rows 1 1 1 1 1 1 1
Fins per inch 22 18 22 22 22 22 22
Outdoor Fan
Diameter – in. 20 20 20 20 20 24 26
Number of blades 2 2 3 3 2 3 2
Motor hp 1/8 1/8 1/4 1/4 1/8 1/6 1/5
CFM 2040 2325 2795 2900 2465 4145 3870
RPM 1075 1075 1075 1075 1075 850 820
watts 144 137 189 186 176 280 233
Shipping weight – lbs. 127 129 140 150 173 182 192
Operating weight – lbs. 120 122 133 143 166 175 185
Electrical Data
Line Voltage Data (Volts-Phase-Hz) 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Maximum overcurrent protection (amps)² 20 25 30 35 40 50 60
Minimum circuit ampacity³ 13 15 18 21 24 29 35
Compressor
Rated load amps 9.7 11.2 12.8 15.4 17.9 21.8 26.4
Locked rotor amps 46 60.8 64 83.9 112 117 134
Condenser Fan Motor
Full load amps 0.7 0.7 1.3 1.3 0.7 1 1.2
Locked rotor amps 1.3 1.3 2.5 2.5 1.3 2 2
Line Voltage Data (Volts-Phase-Hz) 208/230-3-60 208/230-3-60 208/230-3-60 208/230-3-60
Maximum overcurrent protection (amps)²
20 30 30 35
Minimum circuit ampacity³
15 18 19 22
Compressor
Rated load amps 10.4 13.2 13.7 16
Locked rotor amps 73 88 83.1 110
Condenser Fan Motor
Full load amps 1.3 0.7 1 1.3
Locked rotor amps 2.5 1.3 2 2
Line Voltage Data (Volts-Phase-Hz) 480-3-60 480-3-60 480-3-60 480-3-60
Maximum overcurrent protection (amps)²
TBD TBD TBD TBD
Minimum circuit ampacity³
TBD TBD TBD TBD
Compressor
Rated load amps TBD TBD TBD TBD
Locked rotor amps TBD TBD TBD TBD
Condenser Fan Motor
Full load amps TBD TBD TBD TBD
Locked rotor amps TBD TBD TBD TBD
¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional
refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

Other manuals for Rheem RA13 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem RA13 Series and is the answer not in the manual?

Rheem RA13 Series Specifications

General IconGeneral
BrandRheem
ModelRA13 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals